Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/09/2004 | Jim Egan | FIRE | REVIEW | Approved | |
09/17/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1) Sheet 4 of calc`s shows that Rdtll=14573 lbs. > 13200lbs. 11% over, then On the next sheet you explain, but it is not clear to me as to what you are trying to show. CLARIFY! |
09/22/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Detail designations on Sheet E3 read "E2". Pls calrify as necessary. 2. On Sheet E2, Note 6, please add requirement to seal to existing fire rating, as necessary. 3. Please specify inverse-time circuit breaker for the Ground Fault and Short Circuit Protection. Reference NEC 610-42 (a). |
10/07/2004 | Peter McLaughlin | ZONING | REVIEW | Passed | |
10/15/2004 | Doug Williams | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/27/2004 | DELMA ROBEY | OUT TO CUSTOMER | Completed |