Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2004 Jim Egan FIRE REVIEW Approved
09/17/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


1) Sheet 4 of calc`s shows that Rdtll=14573 lbs. > 13200lbs. 11% over, then
On the next sheet you explain, but it is not clear to me as to what you are
trying to show. CLARIFY!
09/22/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Detail designations on Sheet E3 read "E2". Pls calrify as necessary.
2. On Sheet E2, Note 6, please add requirement to seal to existing fire rating, as necessary.
3. Please specify inverse-time circuit breaker for the Ground Fault and Short Circuit Protection. Reference NEC 610-42 (a).
10/07/2004 Peter McLaughlin ZONING REVIEW Passed
10/15/2004 Doug Williams ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2004 DELMA ROBEY OUT TO CUSTOMER Completed