Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2004 JIM EGAN FIRE REVIEW Approved
08/23/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/23/2004 DAN CASTRO ZONING REVIEW Approved
08/23/2004 MELISSA POULIN WWM REVIEW Approved
08/23/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/23/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the ventilation for this project meets the requirements of Section 403.3, IMC 2000.
08/23/2004 ROBERT SHERRY WATER REVIEW Approved
08/24/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03806 DENIED 8/24/04
1. Provide CB on Pnl P1 for AC-1.
2. Account for continuous load on both AC-1 and AC-2 in panel load calculations.
3. P2, Ckts 6, 8, 10, and 12 all appear to have 720 VA, not 540.
4. P2-18 appears to have 360 VA, not 180.
5. Please count show windows and signs as continuous loads in load calculations.
6. Up-Over-Down is not an acceptable method to attenuate fault current for downstream panels. Either fully rate or series rate panels for AFC.
09/07/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied