Permit Number: T04CM03800
Parcel: 126011250

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03800
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2004 JIM EGAN FIRE REVIEW Approved
08/18/2004 DAVE MANN PLUMBING-COMMERCIAL REVIEW Approved
08/18/2004 ANY BUILDING-COMMERCIAL REVIEW Approved
08/18/2004 DAVE MANN MECHANICAL-COMMERCIAL REVIEW Approved
08/18/2004 DAN CASTRO ZONING REVIEW Approved
08/18/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03800/1 DENIED 8/18/04
1. Add entire new AC load to calculation. According to the Panel Schedule such load at 125% is (2) (2625) = 5250, which is higher than indicated on the load calc. Carry calculations through.
2. Clarify voltage on the panels. Suggest that they are 240/120V, not just 120.
3. Provide power requirements for new AC units on Mechanical Equipment Schedule.
08/19/2004 MELISSA POULIN WWM REVIEW Passed
08/19/2004 LLESNY1 ENGINEERING REVIEW Needs Review
08/19/2004 LLESNY1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2004 LISA LESNY OUT TO CUSTOMER Completed