Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03800
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/18/2004 | DAVE MANN | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/18/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/18/2004 | DAVE MANN | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/18/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 08/18/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM03800/1 DENIED 8/18/04 1. Add entire new AC load to calculation. According to the Panel Schedule such load at 125% is (2) (2625) = 5250, which is higher than indicated on the load calc. Carry calculations through. 2. Clarify voltage on the panels. Suggest that they are 240/120V, not just 120. 3. Provide power requirements for new AC units on Mechanical Equipment Schedule. |
| 08/19/2004 | MELISSA POULIN | WWM | REVIEW | Passed | |
| 08/19/2004 | LLESNY1 | ENGINEERING | REVIEW | Needs Review | |
| 08/19/2004 | LLESNY1 | WATER | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/19/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |