Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2004 Gerry Koziol WWM REVIEW Approved
10/05/2004 Neil Saunders BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project #T04CM03789

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen and pencil corrections on final prints will not be acceptable. To avoid delays ensure all corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plan

1. Tempered glass is required over new bathtub if glass is within 60" of drain per R308.4.

Structural Plan

1. Show location of headers on roof framing plan, as well as header for new 7' arch from existing living room to new family room.
2. Detail gable end bracing connections.
3. Specify and detail all over-framing. If solid sheathing is used on the lower trusses, provide minimum openings of 22" by 30" for access and ventilation into over-framed areas (>30 S.F.). If solid sheathing is not used on lower trusses, provide details for bracing of top chord of lower trusses.
4. Detail 1/1 on foundation plan - This detail seems to be confused with 1/2.
5. 1/2 & 2/2 - dimension 6" from bottom of sill.
6. How is existing attic space ventilated? Also, Vent calculations show new addition at 555 sq. ft. while the site plan claims the addition at 710 sq. ft. Clarify.

Plumbing, Mechanical and Electrical Plans

1. Provide total fixture count for all fixtures in house. Provide size of supply line from meter to house.
2. Size return air shall duct per IRC sections M1602.2 and M1603.1. (heat pump / air conditioner - 6 sq. in. / 1000 BTU) (1ton cooling = 12000 BTU). Min 18" dia.
3. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. Consider putting all smoke detectors on one circuit to provide interconnectivity.
4. Show electrical outlets in rooms that have been expanded.
5. Check spacing of electrical outlets in new rooms per E3801.2.1.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2004 LISA LESNY OUT TO CUSTOMER Completed
10/25/2004 ANGIE SHOFFSTALL REJECT SHELF Completed