Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2004 JIM EGAN FIRE REVIEW Approved
08/17/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the fixture unit calculations; a clothes washer is 10 water fixture units.
2. Provide complete water and waste riser diagrams.
08/17/2004 ROBERT SHERRY WATER REVIEW Approved
08/17/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the ventilation calculations by A/C unit.
2. Provide listing information from the dryer manufacturer to show that the 3.5"x10" duct is suitable for the intended use.
08/19/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/25/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
08/26/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
09/09/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
09/16/2004 TACHONG1 WWM REVIEW Needs Review