Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03783
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/17/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the fixture unit calculations; a clothes washer is 10 water fixture units. 2. Provide complete water and waste riser diagrams. |
| 08/17/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/17/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the ventilation calculations by A/C unit. 2. Provide listing information from the dryer manufacturer to show that the 3.5"x10" duct is suitable for the intended use. |
| 08/19/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/25/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 08/26/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 09/09/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/16/2004 | TACHONG1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/16/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |