Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM03782
Parcel: 13316030E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03782
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2004 JIM EGAN FIRE REVIEW Approved
08/17/2004 DAN CASTRO ZONING REVIEW Approved
08/18/2004 DAVE MANN PLUMBING-COMMERCIAL REVIEW Approved
08/18/2004 ANY BUILDING-COMMERCIAL REVIEW Approved
08/18/2004 DAVE MANN MECHANICAL-COMMERCIAL REVIEW Passed
08/20/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/20/2004 MELISSA POULIN WWM REVIEW Approved
08/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03782 DENIED 8/18/04
1. Provide a legend/key to symbols to clarify existing from relocated from demolished equipment.
2. Provide a scaled drawing showing location of new transformer. Clarify such transformer mounting.
3. Demonstrate compliance of new transformer with Working Clearances, Headroom, and Dedicated Equipment Space per NEC 110.26.
4. Transformer shall be grounded as a Separately Derived System per NEC 250.30.
5. Please provide catalogue cut number or cut sheet for the new transformer. Single phase 277V does not appear to be a stock item.
6. Protect the secondary conductors of the transformer per NEC 240.20 (C), or justify otherwise.
10/05/2004 ROBERT SHERRY WATER REVIEW Approved