Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03782
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/17/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 08/18/2004 | DAVE MANN | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/18/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/18/2004 | DAVE MANN | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 08/20/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 08/20/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 08/20/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM03782 DENIED 8/18/04 1. Provide a legend/key to symbols to clarify existing from relocated from demolished equipment. 2. Provide a scaled drawing showing location of new transformer. Clarify such transformer mounting. 3. Demonstrate compliance of new transformer with Working Clearances, Headroom, and Dedicated Equipment Space per NEC 110.26. 4. Transformer shall be grounded as a Separately Derived System per NEC 250.30. 5. Please provide catalogue cut number or cut sheet for the new transformer. Single phase 277V does not appear to be a stock item. 6. Protect the secondary conductors of the transformer per NEC 240.20 (C), or justify otherwise. |
| 10/05/2004 | ROBERT SHERRY | WATER | REVIEW | Approved |