Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM03735
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2005 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a fire/smoke damper for the supply duct serving room 117. |
| 01/18/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the provided schedule of waste fixture units for all plumbing fixtures by coordinating with the fixtures shown on the plumbing plan and using the values shown in Table 7-3, UPC 1994. Reference Section 703.1, UPC 1994. Note: only 3 water closets are shown on the drawing, not 4; a urinal has only 2 waste fixture units; and not all of the sinks appear to be bar sinks (i.e. S-1 and S-3 appear to be commercial sinks). 2. Revise the provided schedule of water fixture units by coordinating with the fixtures shown on the plumbing plan and using the values (public) shown in Tables 6-3 or A2, UPC 1994. Include the total number of each fixture being installed and all existing fixtures being supplied by the same meter. Reference Section 610.3, UPC 1994. Note: only 3 water closets are shown on the drawing, not 4; not all of the sinks appear to be bar sinks (i.e. S-1 and S-3 appear to be commercial sinks), and the water fixture units for items not listed in Table 6-3 should be based on the water connection sizes as shown at the bottom of Table 6-3 for Public Use (e.g. film developer or dentist chair). 3. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps (e.g. each dental chair) may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/27/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 01/27/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |