Permit Number: T04CM03735
Parcel: 10602011F

Address:
3922 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM03735
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2004 Robert Suba ELECTRICAL-COMMERCIAL REVIEW Approved
11/30/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not adequately addressed. Provide calculations demonstrating adequate ventilation. Reference Sections 401 and 403.3, IMC 2000.
2. Provide information about the hood for the hot plate and show how it meets the requirements shown in Section 502, IMC 2000. No additional information was received along with the response to comments. Provide information about the processing conducted under the hood (e.g. materials and temperatures) and the hood design calculations.
11/30/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the provided schedule of waste fixture units for all plumbing fixtures by coordinating with the fixtures shown on the plumbing plan and using the values shown in Table 7-3, UPC 1994. Reference Section 703.1, UPC 1994.
2. Revise the provided schedule of water fixture units by coordinating with the fixtures shown on the plumbing plan and using the values (public) shown in Tables 6-3 or A2, UPC 1994. Include the total number of each fixture being installed and all existing fixtures being supplied by the same meter. Reference Section 610.3, UPC 1994.
3. Coordinate the natural gas pipe sizing calculations with the equipment requirements as shown on sheet ES-8. Reference Section 1217.0, UPC 1994 with AZ State amendments.
4. Revise sheets P-4 (to show key note #6) and P-2 (to show keynote #1).
12/02/2004 Gerry Koziol WWM REVIEW Approved
12/22/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2005 BETH GRANT OUT TO CUSTOMER Completed
01/12/2005 ANGIE SHOFFSTALL REJECT SHELF Completed