Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM03721
Parcel: 11301146Z

Address:
1767 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03721
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2004 JIM EGAN FIRE REVIEW Approved
08/13/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/13/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE ACCESSIBILITY STATEMENT 20% COST OF CONSTRUCTION SHOWING CALCULATIONS AND DRAWINGS FOR CHANGES MADE OR A STATEMENT ON DRAWINGS STATING EXISTING SITE MEETS ACCESSIBILTY REQUIREMENTS. IBC CHAPT 11 & 34 , ANSI A117.1.
2) COMPLETE CODE DATA ANALYSIS CHECK LIST.
08/13/2004 ROBERT SHERRY WATER REVIEW Approved
08/13/2004 DAN CASTRO ZONING REVIEW Approved
08/13/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation for the new spaces per Section 403, IMC 2000.
2. Condensate from the fan coil unit may terminate over a roof drain only if the roof drain itself terminates in an area that will not produce surface runoff. Reference local amendments to Section 307.2.4, IMC 2000.
3. Provide a secondary drain for the fan coil unit. Reference Section 307.2.3, IMC 2000.
08/13/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/13/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
08/17/2004 TACHONG1 WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2004 TAMI ACHONG OUT TO CUSTOMER Completed