Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM03719
Parcel: 141148090

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03719
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2004 JIM EGAN FIRE REVIEW Approved
08/13/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/13/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE ACCESSIBILITY STATEMENT 20% COST OF CONSTRUCTION SHOWING CALCULATIONS AND DRAWINGS FOR CHANGES MADE OR A STATEMENT ON DRAWINGS STATING EXISTING SITE MEETS ACCESSIBILTY REQUIREMENTS. IBC CHAPT 11 & 34 , ANSI A117.1.
2) COMPLETE CODE DATA ANALYSIS CHECK LIST.
08/13/2004 ROBERT SHERRY WATER REVIEW Approved
08/13/2004 DAN CASTRO ZONING REVIEW Approved
08/13/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation for the new spaces per Section
403, IMC 2000.
2. Condensate from the fan coil unit may terminate
over a roof drain only if the roof drain itself
terminates in an area that will not produce surface
runoff. Reference local amendments to Section
307.2.4, IMC 2000.
3. Provide a secondary drain for the fan coil
unit. Reference Section 307.2.3, IMC 2000.
4. Clarify how the maintenance access to the fan coil is kept clear with a transfer grille and duct located in the maintenance zone. Reference Section 306, IMC 2000.
08/13/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/13/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
08/18/2004 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/18/2004 BETH GRANT OUT TO CUSTOMER Completed