Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2004 JIM EGAN FIRE REVIEW Approved Type 1 Kitchen exhaust hood w/ fire suppression system required.
08/12/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed Resize the gas line to the new range. Reference Section 1217.1, UPC 1994.
08/12/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1)Clarify and explain mixed occupancy use.
2)Provide site plan with property lines.
3) Show all bldgs and locate tenant space clarifying location of restroom and calculations justifying adequate fixtures are provided. Dimension distance from restroom to tenant space along a accessable path.
4)Where is sht. A-3?
5) Clarify walls being removed are non-bearing or provide structural analysis.
6) Provide structural analysis for kitchen hoods.
7) Additional review may be required depending on what is shown on sht. A-3.
08/12/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved Provide Type I grease hoods for the three ranges located in the cooking classroom. Reference Section 507..2.2, IMC 2000.
08/12/2004 ANY ENGINEERING REVIEW Approved Site plan required.
08/18/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03713 DENIED 8/12/04
1. Conductor size for oven. #12 too small for 40A CB.
2. Receptacles are on Ckt B-1 on Electrical Plan. Panel Schedule indicates lighting. Please clarify.
3. Ckt B-16 appears to have 1080 VA, not 900.
4. Panel schedules indicate that certain circuits are counted as having 125% demand for continuous load. Yet no circuits are identified as such. Please account for continuous loading on panels, and add 25% for the highest motor.
5. Please add a load calculation for the capacity of the service.
6. It appears that Phase B of Panel A is 17535 VA, not 16,535.
08/18/2004 DAN CASTRO ZONING REVIEW Approved
08/19/2004 LLESNY1 WWM REVIEW Passed
08/19/2004 LLESNY1 WATER REVIEW Passed