Permit Number: T04CM03704
Parcel: 13426001B

Address:
710 S KOLB RD

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM03704
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
08/11/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/12/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03704 DENIED 8/12/04
1. Provide a scaled electrical site plan with location of all equipment, poles, and existing service/panel.
2. Specify panel and circuit number for new poles.
3. See Structural/Building Plans Examiner regarding pole and foundation details.
4. Specify depth of conduit fill.
5. TEP published available fault current is 13,900 A. Please indicate so on plans, and provide fault calculations to demonstrate that the breakers for the new circuit are rated for the AFC available at that point.
6. Verify compliance with Lighting Ordinance Sec 5.1.