Permit Number: T04CM03700
Parcel: 10321671B

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM03700
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
08/26/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T04CM03700 .. 2500 N SILVERBELL , SUITE #180 .. DGL .. 8/27/04 ..
COMMENTS - 1ST REVIEW

S1. Provide connection details from partitions to structure above including materials of construction and fasteners ( type, size , spacing /number) ref drawing A3.
S2. Show connections at soffit , ref detail 13/A3.
S3. Verify glazing at checkin counter ref drawing A4.
S4. Show clearances inside accessible toilet room comply with ANSI A117.1 - 98ed Sec 404, Fig 404.2.4.1 (a), Sec 604 , Fig 604.3.1 and Sec 606 , Fig 305.5 and Fig 306.2.

Questions ? Call Douglas Laakso , Structural Plans Examiner with City of Tucson , Development Services Department at (520) 791-5550 x 1111.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2004 LISA LESNY OUT TO CUSTOMER Completed
08/30/2004 ANGIE SHOFFSTALL REJECT SHELF Completed