Permit Number: T04CM03699
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03699
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2004 JIM EGAN FIRE REVIEW Denied 1. Occupant load exceeds 30-Two exits required.
2. Exits through intervening rooms shall comply with 2000 IBC Sec. 1004.2.3.(No locking hardware Doors 106 & 109.)
08/11/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/11/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/11/2004 ROBERT SHERRY WATER REVIEW Approved
08/11/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the ventilation for the new classroom meets the requirements of Section 403.3, IMC 2000.
08/25/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
08/25/2004 JIM TATE ENGINEERING REVIEW Approved
08/26/2004 LLESNY1 WWM REVIEW Needs Review
08/26/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2004 LISA LESNY OUT TO CUSTOMER Completed