Permit Number: T04CM03681
Parcel: 11005314C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T04CM03681
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2004 Paul Machado ENGINEERING REVIEW Approved
09/17/2004 Jim Egan FIRE REVIEW Denied PROVIDE FIRE SPRINKLER SYSTEM DESIGN CRITERIA ON PLAN.
09/23/2004 Daniel Castro ZONING REVIEW Denied Building plans submitted for review do not match the approved development plan case number D03-0023. Building sizes and footprints have changed. Prior to the approval of the building plans by the Zoning Review Section the following must occur: Three copies of the revised development plan sheets 1 and 2 are required to be submitted for Zoning and Engineering Review. Revised development plan sheets 1 and 2 must provide all revised information (i.e. floor area ratio, parking, loading calculation). The 3 sets must be submitted to the Zoning Review Section and the review period is usually 5 working days. Once the revised development plan is approved the building plans may then be approved by Zoning Review.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2004 TAMI ACHONG OUT TO CUSTOMER Completed
09/27/2004 ANGIE SHOFFSTALL REJECT SHELF Completed