Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03676
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/10/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM03676 DENIED 8/10/04 1. Provide lighting fixture schedule/cut sheets. Then branch circuit, feeder, and service loading will be evaluated. 2. Keynote 7 on Electrical Power Plan appears to refer to Circuit "JAY-1-35", not "JAY-1-39." |
| 08/12/2004 | DROBEY1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 08/12/2004 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 08/12/2004 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 08/12/2004 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/12/2004 | DROBEY1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/12/2004 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
| 08/12/2004 | DROBEY1 | WATER | REVIEW | Needs Review |