Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03675
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/12/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show ventilation calculations for the space. Reference Sections 403.3 and 403.3.2, IMC 2000. |
| 08/16/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
| 08/16/2004 | LLESNY1 | ZONING | REVIEW | Needs Review | |
| 08/16/2004 | LLESNY1 | ENGINEERING | REVIEW | Needs Review | |
| 08/16/2004 | LLESNY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | 1)JUSTIFY ONLY ONE RESTROOM. OCCUPANT LOAD REQUIRES TWO. 2) CLARIFY / PROVIDE SITE PLAN SHOWING BLDG AREA, FIRE WALL SEPARATION AND CONSTRUCTION MATERIALS. 3) ADDRESS ACCESSABILITY NEED ESTIMATE FOR CONSTRUCTION COST AND 20% PUT TOWARDS ACCESSIBILITY PER IBC CHAPT 11 & 34 AND ANSI A117.1 1998. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/16/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |