Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03673
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/10/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/10/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/10/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/10/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 08/10/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/10/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 08/11/2004 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 08/11/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM03673 DENIED 8/10/04 1. It appears that Phase B is overloaded at 208 amps, considering feeder size and fuse. This is considering that Ckt 3, with 6 receptacles, would have 1.1 VA, nto 0.6. 2. Please confirm that 25% has been allocated for the largest motor on Panel C. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/07/2004 | SUE REEVES | APPROVAL SHELF | Completed |
| 09/07/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |