Review Details: COMMERCIAL TI

Permit Number - T04CM03673
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2004 JIM EGAN FIRE REVIEW Approved
08/10/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/10/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
08/10/2004 ROBERT SHERRY WATER REVIEW Approved
08/10/2004 DAN CASTRO ZONING REVIEW Approved
08/10/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/10/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
08/11/2004 GERRY KOZIOL WWM REVIEW Passed
08/11/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03673 DENIED 8/10/04
1. It appears that Phase B is overloaded at 208 amps, considering feeder size and fuse. This is considering that Ckt 3, with 6 receptacles, would have 1.1 VA, nto 0.6.
2. Please confirm that 25% has been allocated for the largest motor on Panel C.