Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM03646
Parcel: 141148090

Review Status: Stopped

Review Details: COMMERCIAL TI

Permit Number - T04CM03646
Review Name: COMMERCIAL TI
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2005 DSTARK1 ENGINEERING REVIEW Stop
08/09/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/09/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied NEED ACTUAL SIZE ARCHITECT SEAL.
MINIMUM SIZE TEXT 10 PT.
08/09/2004 ANY WWM REVIEW Stopped
08/09/2004 ANY ZONING REVIEW Stopped
08/09/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. All fonts used on the plans shall be no smaller than 10 points.
2. Provide ventilation air per Section 403.3, IMC 2000.
3. Clarify how the maintenance zone for the fan coil is being kept clear if the transfer grille is located in the maintenance zone.
4. The condensate from the fan coil may be terminated over a storm drain only if the storm drain itself terminates in an area that is capable of absorbing the flow without surface drainage. Reerence Section 307.2.1, IMC 2000, as amended by the City of Tucson.
08/09/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/09/2004 ROBERT SHERRY WATER REVIEW Approved
08/09/2004 ANY FIRE REVIEW Stopped

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2004 ANY APPROVAL SHELF Stopped
08/09/2004 ANY OUT TO CUSTOMER Stopped
08/09/2004 ANY REJECT SHELF Stopped