| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2004 | ANY | ENGINEERING | REVIEW | Approved | |
| 08/05/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that the accessibilty of the water heater complies with Section 511.4, UPC 1994. 2. Show how the water piping has been sized. Reference Section 610.1, UPC 1994. 3. Provide riser diagrams for the waste and water supply systems. |
| 08/05/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM03609 DENIED 8/5/04 1. #6 GND between 150 KVA X'FMR and 200A fuse shall be sized at #4. Reference NEC Table 250.66 Note a. |
| 08/05/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/05/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/05/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the outside air calculations for the QA and Packaging rooms. Coordinate with the HVAC floor plan and the architectural floor plan. 2. Identify the scope of work for this project. |
| 09/07/2004 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 09/07/2004 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 09/07/2004 | DROBEY1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/07/2004 | DELMA ROBEY | OUT TO CUSTOMER | Completed |