Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2004 ANY ENGINEERING REVIEW Approved
08/05/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that the accessibilty of the water heater complies with Section 511.4, UPC 1994.
2. Show how the water piping has been sized. Reference Section 610.1, UPC 1994.
3. Provide riser diagrams for the waste and water supply systems.
08/05/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03609 DENIED 8/5/04
1. #6 GND between 150 KVA X'FMR and 200A fuse shall be sized at #4. Reference NEC Table 250.66 Note a.
08/05/2004 ROBERT SHERRY WATER REVIEW Approved
08/05/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
08/05/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the outside air calculations for the QA and Packaging rooms. Coordinate with the HVAC floor plan and the architectural floor plan.
2. Identify the scope of work for this project.
09/07/2004 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
09/07/2004 DROBEY1 WWM REVIEW Needs Review
09/07/2004 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2004 DELMA ROBEY OUT TO CUSTOMER Completed