Permit Number: T04CM03604
Parcel: 110102590

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03604
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
08/04/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
08/05/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that the water heater complies with the access requirements of Section 511.4, UPC 1994.
08/05/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
08/05/2004 ROBERT SHERRY WATER REVIEW Approved
08/05/2004 JIM EGAN FIRE REVIEW Approved
08/05/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify that the quantity of outside air supplied to the space complies with Section 403.3.2, IMC 2000.
08/05/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/10/2004 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2004 TAMI ACHONG OUT TO CUSTOMER Completed