Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03604
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 08/04/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 08/05/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that the water heater complies with the access requirements of Section 511.4, UPC 1994. |
| 08/05/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/05/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/05/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/05/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Verify that the quantity of outside air supplied to the space complies with Section 403.3.2, IMC 2000. |
| 08/05/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/10/2004 | TACHONG1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/10/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |