Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM03580
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/14/2005 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/18/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Second request. Appliances to be directly connected to the water supply system (e.g. film processor, dental chairs, etc.) that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994. Note: the term "industrial water" implies that the water to the water filter will not be used as potable water. Please indicate how the water will be used for the dental chairs. |
01/21/2005 | Gerry Koziol | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/27/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |
01/27/2005 | SUE REEVES | REJECT SHELF | Completed |