Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information about the hood for the hot plate and show how it meets the requirements shown in Section 502, IMC 2000. The information shown on sheet A-4.1 is insufficient to show that the hood meets the code requirements. Provide information about the processing conducted under the hood (e.g. materials and temperatures) and the hood design calculations.
11/29/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a schedule of waste fixture units for all plumbing fixtures using the values shown in Table 7-3, UPC 1994. Include the total number of each fixture being installed. Reference Section 703.1, UPC 1994. The data provided on sheet P-2 is not from the 1994 edition of the UPC.
2. Provide a schedule of water fixture units for all plumbing fixtures using the values shown in Tables 6-3 or A2, UPC 1994. Include the total number of each fixture being installed. Reference Section 610.3, UPC 1994. The data provided on sheet P-2 is not from the 1994 edition of the UPC.
3. Appliances to be directly connected to the water supply system (e.g. film processor, dental chairs, etc.) that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
4. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference Section 707.4, UPC 1994.
12/03/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
12/07/2004 Gerry Koziol WWM REVIEW Denied Needs 8th floor WW credit evaluation.
12/27/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Approved