Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T04CM03580
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/29/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information about the hood for the hot plate and show how it meets the requirements shown in Section 502, IMC 2000. The information shown on sheet A-4.1 is insufficient to show that the hood meets the code requirements. Provide information about the processing conducted under the hood (e.g. materials and temperatures) and the hood design calculations. |
11/29/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a schedule of waste fixture units for all plumbing fixtures using the values shown in Table 7-3, UPC 1994. Include the total number of each fixture being installed. Reference Section 703.1, UPC 1994. The data provided on sheet P-2 is not from the 1994 edition of the UPC. 2. Provide a schedule of water fixture units for all plumbing fixtures using the values shown in Tables 6-3 or A2, UPC 1994. Include the total number of each fixture being installed. Reference Section 610.3, UPC 1994. The data provided on sheet P-2 is not from the 1994 edition of the UPC. 3. Appliances to be directly connected to the water supply system (e.g. film processor, dental chairs, etc.) that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994. 4. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference Section 707.4, UPC 1994. |
12/03/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/07/2004 | Gerry Koziol | WWM | REVIEW | Denied | Needs 8th floor WW credit evaluation. |
12/27/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/12/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |
01/12/2005 | SUE REEVES | REJECT SHELF | Completed |