Permit Number: T04CM03580
Parcel: 133231410

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03580
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2004 Jim Egan FIRE REVIEW Approved
08/20/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000.
2. Refer to Section 606, IMC 2000 for the requirements for in-duct smoke detectors.
3. Provide information about the hood for the hot plate and show how it meets the requirements shown in Section 502, IMC 2000.
08/20/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. The relevant code for the City of Tucson is the 1994 Uniform Plumbing Code with State of Arizona amendments.
2. Provide a schedule of waste fixture units for all plumbing fixtures using the values shown in Table 7-3, UPC 1994. Include the total number of each fixture being installed. Reference Section 703.1, UPC 1994.
3. Provide a schedule of water fixture units for all plumbing fixtures using the values shown in Tables 6-3 or A2, UPC 1994. Include the total number of each fixture being installed. Reference Section 610.3, UPC 1994.
4. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2000, for business occupancy.
5. Verify the water pressure used for the calculations.
6. Revise the water pressure calculations to include the pressure drop due to the reduced pressure backflow preventer. Reference Section 610.2, UPC 1994.
7. One of the specified fixtures (Haws eyewash) requires a minimum pressure greater than the 25-PSI used in the water pipe sizing calculations. Revise calculations as necessary. Reference Section 608.1, UPC 1994.
8. Provide natural gas pipe sizing calculations. Include gas pressures and developed pipe lengths on plans. Reference Section 1217.0, UPC 1994 with AZ State amendments. Note: altitude is greater than 2000 feet.
08/20/2004 ROBERT SHERRY WATER REVIEW Approved
08/24/2004 Gerry Koziol WWM REVIEW Denied Needs 8th floor WW credit evaluation.
08/30/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please add the following note: "All work in patient care areas shall be in accordance with NEC 517-13."
2. J-boxes have been provided on electrical plans for dental chairs. Sheet ES-1 specifies a hospital-grade plug. Please clarify.
3. Provide X-Ray disconnecting means per NEC 517-72, readily accessible from Control Boxes, or justify otherwise. Reference Notes 4,5,6 Sheet E-4.
4. Per Sheet P-1, Water Heater is 480V. However, it is powered at 208V from Panel PC. Coordinate with Plumbing and clarify.
5. Per Sheet ES-5, Air Compressor is called out as CA827D, 208/230, 13.4 A. Sheet E-4 Keynote calls out 16.2 A. Please coordinate and clarify. And note that even at 16.2A, the overcurrent protection at 1.5 factor per NEC 422.11 (e) (3) shall not exceed 25A.
6. Panel PA feeder Equipment Grounding Conductors in parallel runs, shall be sized per NEC Table 250.122 as #3 minimum.
7. Regarding Note 5 Sheet E-2, identify specific line side and load side overcurrent protective devices in all cases of series rating, with specific rating line side and load side devices.
8. Provide available fault current at all relevant points of the electrical system.
9. Provide load calculations for service equipment and conductors.
09/03/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Plans show a corridor. A corridor shall be protected by 1-hr wall construction.
All doors in corridor shall be protected with 20 minute doors with auto. Closers.
All openings within the rated corridor shall be protected with 1-hr. rated assemblies.
2) Provide emergency power for egress illumination. Sec. 1003.2.11.2

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2004 TAMI ACHONG OUT TO CUSTOMER Completed
09/09/2004 TAMI ACHONG REJECT SHELF Completed