The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM03576
Parcel: 129080180

Address:
1747 E 23RD ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T04CM03576
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2004 Andrew Connor LANDSCAPE REVIEW Denied 1) Revise the plans to provide masonry screen walls per LUC Table 3.7.2-I to screen the commercial land use and the loading areas from adjacent residentially zoned properties along the northerly and westerly boundaries.

2) Revise the plans to include interior landscape borders per LUC Table 3.7.2-I to buffer the commercial land use a from adjacent residentially zoned properties along the northerly and westerly boundaries.
11/02/2004 ANDREW CONNOR NPPO REVIEW Approv-Cond
11/19/2004 DAN CASTRO ZONING HC SITE REVIEW Approved
11/19/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were
addressed. (CODE SECTION/ DEVELOPMENT STANDARD)

1. LUC Sec. 3.2.6.4 Perimeter Yard Indicator "DD" requires a minimum building setback of 39 feet from the north and west property lines. The proposed site plan provides a building setback of 24.63 feet from the west property line and a building setback of .67 feet from the north property line. Proposed building height is 26 feet. (D.S. 2-02.2.1.A.7)

2. Since a Lot Development Option (LDO) will be applied for, please provide a copy of the decision letter with the resubmittal of this plan. If approved, please list the LDO case number, date of approval, setback modifications granted, and conditions imposed as a general note.

3. Review of this plan by the Zoning Review Section may be done over the counter. Please call me to set an appointment.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
11/29/2004 Loren Makus ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/08/2005 JKELSO1 OUT TO CUSTOMER Completed