Permit Number: T04CM03576
Parcel: 129080180

Address:
1747 E 23RD ST

Review Status: Completed

Review Details: SITE

Permit Number - T04CM03576
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2004 Jim Egan FIRE REVIEW Approved
08/04/2004 Joseph Linville LANDSCAPE REVIEW Denied 1) Revise the plans to provide masonry screen walls per LUC Table 3.7.2-I to screen the commercial land use and the loading areas from adjacent residentially zoned properties along the northerly and westerly boundaries.

2) Revise the plans to include interior landscape borders per LUC Table 3.7.2-I to buffer the commercial land use a from adjacent residentially zoned properties along the northerly and westerly boundaries.

3) Provide documentation in writing of any City Engineer approvals to locate code required landscaping within the public right-of-way. LUC 3.7.2.4.A.2

4) Revise the plans to include plant protection per LUC 3.7.2.3.B.

5) Revise the plans to provide suitable barriers at the perimeter of the vehicular use area per DS 3-05.2.3.C.1

6) Provide screening of the loading area from 23rd St. per LUC Table 3.7.2-I

7) A minimum of three trees is required within the street landscape border. LUC 3.7.2.4

8) Revise the plans as necessary to ensure that the public right-of-way area will be treated with an appropriate dust control material per LUC 3.7.2.4.A.3

9) Indicate on the plans how the site makes maximum use of site storm water runoff for supplemental on-site irrigation purposes. The landscape plan shall indicate use of
all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area. Include grading information per DS 2-07.2.2.B

10) Include documentation of any variance cases with any resubmittal. Reference related cases by number in the lower right corner of the plans. DS 2-07.2.1
08/05/2004 JOE LINVILLE NPPO REVIEW Denied Revise as necessary to correspond with the site and landscape plans.
08/18/2004 Loren Makus ENGINEERING REVIEW Denied DATE: August 19, 2004
TO: David Poore
SUBJECT: Site Plan: Oasis Bottled Water Warehouse
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04CM03576

SUMMARY: The Site Plan was reviewed by Development Services Department, Engineering Division on August 19, 2004. It was not approved. Please address the following comments.

Site Plan Comments:

1. The refuse container location is not accessible in accordance with the development standard. (DS 6-01.3.1.A)
2. Provide 10 feet clear between the bollards. (DS 6-01.4.2.C.1)
3. The cut and fill quantities on the site plan do not correspond with the grading and paving plan. Revise the plans so that they are in agreement.
4. Show how stormwater runoff will be directed to the water harevesting areas.

Revise the Site Plan, to address all of these comments and resubmit two copies of each for review. Include a letter explaining how each comment has been addressed. A separate grading permit application must be submitted and approved for this project.
Loren Makus
Senior Engineering Associate
Engineering Division
Development Services
08/20/2004 DAN CASTRO HANDICAP-SITE REVIEW Denied Indicate graphically or by note how the pedestrian sidewalks are physically separated from the vehicular use area (i.e. curbing, grade separation, barriers, railings, or other means). (D.S. 2-02.2.1.A.12)
08/20/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were
addressed. (CODE SECTION/ DEVELOPMENT STANDARD)

1. List the legal description of the property (Neff Lot 2 Blk2). (D.S. 2-02.2.1.A.2)

2. LUC Sec. 3.2.6.4 Perimeter Yard Indicator "DD" requires a minimum building setback of 39 feet from the north and west property lines. The proposed site plan provides a building setback of 24.63 feet from the west property line and a building setback of .67 feet from the north property line. Proposed building height is 26 feet. (D.S. 2-02.2.1.A.7)

3. Indicate graphically or by note how the pedestrian sidewalks are physically separated from the vehicular use area (i.e. curbing, grade separation, barriers, railings, or other means). (D.S. 2-02.2.1.A.12)

4. If a Lot Development Option (LDO) is applied for, please provide a copy of the decision letter. If approved, please list the LDO case number, date of approval, setback modifications granted, and conditions imposed as a general note.

5. Review of this plan by the Zoning Review Section may be done over the counter. Please call me to set an appointment.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
08/23/2004 ANGIE SHOFFSTALL REJECT SHELF Completed