Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T04CM03565
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/31/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water pressure calculations; revise pipe sizes as required. Reference Section 610.4, UPC 1994 2. Revise water fixture units per Table 6-3, UPC 1994. |
08/31/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/02/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
09/02/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM03565 DENIED 8/31/04 1. Exterior lighting fixtures may not be incandescent. Reference 2000 IECC 805.5. 2. First review called for lighting cut sheets. Without such cut sheet for exterior lighting fixture, it is not possible to evaluate such fixture for compliance with the Outdoor Lighting Ordinance. 3. Water Heater conductor shall be a minimum of #10 per NEC 240.3 (D). |
09/02/2004 | TACHONG1 | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/02/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |