Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM03565
Parcel: 117141070

Address:
58 W CUSHING ST

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T04CM03565
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water pressure calculations; revise pipe sizes as required. Reference Section 610.4, UPC 1994
2. Revise water fixture units per Table 6-3, UPC 1994.
08/31/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/02/2004 TACHONG1 WWM REVIEW Needs Review
09/02/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03565 DENIED 8/31/04
1. Exterior lighting fixtures may not be incandescent. Reference 2000 IECC 805.5.
2. First review called for lighting cut sheets. Without such cut sheet for exterior lighting fixture, it is not possible to evaluate such fixture for compliance with the Outdoor Lighting Ordinance.
3. Water Heater conductor shall be a minimum of #10 per NEC 240.3 (D).
09/02/2004 TACHONG1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2004 TAMI ACHONG OUT TO CUSTOMER Completed