Permit Number: T04CM03560
Parcel: 124040120

Address:
1435 E 2ND ST

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM03560
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/03/2004 JIM EGAN FIRE REVIEW Approved
08/03/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
08/03/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/03/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
08/03/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
08/04/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03560 DENIED 8/3/04
1. Show location of existing Panel A on plans, and provide fault current rating, and fault calculations for AFC at this panel.
2. Please check loading of Ckt B-9,11 for AC-24. My count would be 2160 VA per phase, which is too much higher than the 1060 VA indicated on the panel schedule.
3. Please check loading of Ckt B-5,7 for AC-21. My count would be 3024 VA per phase, which is too much higher than the 2055 VA indicated on the panel schedule.
4. Please recheck VA counts for other AC units and correct as necessary.