Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM03560
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/03/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/03/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 08/03/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/03/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/03/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/04/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM03560 DENIED 8/3/04 1. Show location of existing Panel A on plans, and provide fault current rating, and fault calculations for AFC at this panel. 2. Please check loading of Ckt B-9,11 for AC-24. My count would be 2160 VA per phase, which is too much higher than the 1060 VA indicated on the panel schedule. 3. Please check loading of Ckt B-5,7 for AC-21. My count would be 3024 VA per phase, which is too much higher than the 2055 VA indicated on the panel schedule. 4. Please recheck VA counts for other AC units and correct as necessary. |