Permit Number: T04CM03553
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03553
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/02/2004 ROBERT SHERRY WATER REVIEW Approved
08/02/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify scope of mechanical work (Note #1, sheet ASP)
08/05/2004 JIM EGAN FIRE REVIEW Denied Inadequate exits. Provide information on retractable room dividers.
08/05/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed
08/10/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied PROVIDE CEILING GRID ATTACMENT DETAIL.
IF REMOVING - REMOVABLE WALL TRACK PROVIDE DETAIL FOR THE TRACK FOR WALL SYSTEM.
08/12/2004 TACHONG1 WWM REVIEW Passed
08/12/2004 TACHONG1 ZONING REVIEW Needs Review
08/12/2004 TACHONG1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2004 TAMI ACHONG OUT TO CUSTOMER Completed