Permit Number: T04CM03542
Parcel: 123021100

Address:
2625 E SENECA ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM03542
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2004 Gerry Koziol WWM REVIEW Approved
11/11/2004 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T04CM03542 11/11 /2004

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

SITE PLAN:
1. Indicate the location of gas line on the property, and where it enters the building.

FOUNDATION PLANS:
. All foundation hold-downs and anchor-bolt spacing for brace walls shall be specified and located.------pahd42 does not meet the 1800# uplift requirement when used closer than 8" to a corner, a hpahd22 does meet this requirement. Change on plans.

FLOOR PLANS:
1. Provide a complete floor plan including all rooms adjacent to new construction. It appears a new wall is being built in the existing house at refrigerator/counter space, what is happening on other side of wall. A window is being infilled at existing house wall at new dining area, what is the romom used for? Indicate all doors, windows, etc.
2. It would be helpful if you would provide a plan of what was existing prior to construction.

ELEVATIONS:
1. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply.---------unvented attic space with insulation against bottom of roof sheathing not allowed when using asphalt shingles-----change detail 3/A4

PLUMBING PLANS:
1. Gas: Provide the length of line to each appliance, BTU demand of each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system per UPC 1217.2.

MECHANICAL PLANS:
1. Clearly indicate on plans where gas pack that is to be replaced is located

ELECTRICAL PLANS:
1. Ground rods for subpanels in an attached are not allowed.
2. Note that two or more 2O AMP small appliance circuits shall be provided to serve all receptacles outlets in the kitchen, breakfast room and dining room. Such circuits shall have no other outlets, per E3603.2 and E3801.3 through E3801.4.5.------------cross reference to panel schedule-------all recepts at kitchen counters are to be gfci
If you have any questions, please contact your assigned plans examiner Terry Stevens at 791-5550, extension 1112.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2004 DHERRON1 OUT TO CUSTOMER Completed
12/06/2004 ANGIE SHOFFSTALL REJECT SHELF Completed