08/05/2004 Jim Egan FIRE REVIEW Approved
08/09/2004 Gerry Koziol WWM REVIEW Approved
08/10/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Passed
08/10/2004 ROBERT SHERRY WATER REVIEW Approved
08/10/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the water connections to the vending machines. Reference Section 103.2.3, UPC 1994.
2. Construct the 2-way cleanout using approved drainage fittings. Reference Section 301.1.3, UPC 1994.
3. Verify the size of the Reduced Pressure Backflow Preventor located after the water meter complies to Section 610.2, UPC 1994.
4. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 1994.
08/16/2004 Loren Makus ENGINEERING REVIEW Denied DATE: August 16, 2004
TO: Andrew Dennehy
SUBJECT: 22nd Street Kiosk
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04CM03496

SUMMARY: The Site Plan was reviewed by Development Services Department, Engineering Division on August 16, 2004. The site plan was not approved. Please address the following comments.

Site Plan Comments:
1) Revise the site plan and grading plan to show how water harvesting will be used to the maximum extent practicable. Show areas that will be depressed to serve as water harvesting areas and show how stormwater will be directed to these areas. (LUC 3.7.4)
2) Show the sight visibiltiy triangles along Herbert Avenue. (DS 2-02.2.1.A.10)
3) Provide estimated cut and fill quantities. (DS 2-02.2.1.A.17)
4) Label 22nd Street as a Major Street and Routes arterial. Label the future right-of-way width. (DS 2-02.2.1.A.19)
5) Show the proposed location of the refuse container and show how it will be serviced by Environmental Services or by a commercial hauler. (DS 2-02.2.1.A.32)

Revise the Site Plan to address all of these comments and resubmit two copies for review. Include a letter explaining how each comment has been addressed.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services
08/25/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. If the intent is to provide landscape and parking lot lighting, show such equipment on the plans. Full design on Electrical Site Plan, with panel and circuit numbers, conductor and conduit size and type, pole and foundation details, and calculations for such poles and foundations sealed by a Registered Structural Engineer for poles over 20' in height.
2. Provide lighting schedules /cut sheets for all fixtures, and identify exact fixture on submitted cut sheets.
3. It appears that there is a fluorescent lighting fixture on the exterior of the building with no attachment. Please clarify.
4. Provide conductor size for Grounding Electrode Conductor.
5. Provide breaker sizes and # of poles for all circuits in this project.
6. 1" conduit appears too small for 3-#1/0 Cu. Please re-evaluate.
7. Provide fault current rating of new equipment.
08/27/2004 Daniel Castro ZONING REVIEW Denied Building plans may not be approved by the Zoning Review Section until the site plan has been approved by all sections and the building plans have been approved by Structural Review.
09/01/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 9/2/04
ACTIVITY NUMBER: T04CM03496
PROJECT NAME: WATER VENDING KIOSK
PROJECT ADDRESS: 215 E. 22ND
ARCHITECT / ENGINEER: ANDREW DENNEHY
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1. SHT. 4 STRUCTURAL CALCULATIONS SPECIFIES LEDGER BOLTS @ 16" O.C. AND SHT. 2 DTL. C SPECIFIES 32" O.C., PLEASE CLARIFY.
2. SHT. 5 STRUCTURAL CALCULATIONS REQUIRES #4 VERTICAL @ 24" O.C. DETAIL 1 SHT. 2 SPECIFIES 48" O.C., PLEASE CLARIFY.
3. NORTH WALL NEEDS TO BE 2 HR WALL PER TABLE 602. NO OPENINGS / PENETRATIONS ALLOWED, THEREFORE SCUPPER FOR DRAINAGE OF ROOF DOES NOT MEET CODE.