Permit Number: T04CM03495
Parcel: 115160330

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03495
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2004 JIM EGAN FIRE REVIEW Approved
07/29/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide descriptions of the new fixtures being installed.
07/29/2004 DAN CASTRO ZONING REVIEW Approved
07/29/2004 ROBERT SHERRY WATER REVIEW Approved
07/29/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/29/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the location of the thermostat and the return for the existing 2-ton A/C unit above office 2.
2. Verify the flowrate of the existing exhaust fan in the restroom meets the requirements of Section 403.3, IMC 2000.
07/30/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
07/30/2004 TACHONG1 WWM REVIEW Needs Review
07/30/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2004 TAMI ACHONG OUT TO CUSTOMER Completed