Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM03477
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2004 | Gerry Koziol | WWM | REVIEW | Approved | |
| 09/30/2004 | Neil Saunders | BUILDING-RESIDENTIAL | REVIEW | Denied | Plan Check Comments - Project T04CM00470 Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. General Requirements 1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned. 2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes. Foundation Plan 1. Braced wall panel is required every 25' as well. Show on long sides of structure. Is building fully sheathed? 2. Panels less than 48" require holdowns. Show location on foundation plan. 3. A, B, H & I are missing from foundation plan. Floor Plan 1. Remove all notes that do not apply. 2. Note and specify that shower enclosures shall have a minimum finished interior area of 1,024 square inches and shall be capable of encompassing a minimum 30" circle per UPC SEC. 410.0. All glass enclosures shall be tempered. 3. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per R307.2 (figure). Structural Plan 1. Provide details for - Post to beam, Post to foundation and Porch rafter connection to wall. 2. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply. Plumbing and Electrical Plan 1. The City of Tucson has adopted the 1994 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code. 2. Revise fixture unit calculation per table 6-3 1994 UPC. Include existing fixture from existing house. Note meter size, supply line size and total developed length to comply with table 6-4 1994 UPC. 3. Note 6 conflicts with callout 12. Clarify. 4. Remove all unnecessary notes. 5. Provide location of 100 amp subpanel. 6. Panel diagram - TEP will not run cable past meter. Clarify. Size feeder cables from existing service to subpanel. If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/01/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/01/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |