Permit Number: T04CM03465
Parcel: 123060690

Address:
1500 N PLUMER AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/NPPO

Permit Number - T04CM03465
Review Name: RESIDENTIAL BLDG/ZONING/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2004 Joseph Linville NPPO REVIEW Passed
09/02/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were
addressed. (CODE SECTION/ DEVELOPMENT STANDARD)

1. Revise the building wall heights to be measured from design grade elevation. The plan submitted shows building elevation heights that are measured from finished floor elevation. Setback requirements may not be verified until the height is provided from design grade to the highest point of the exterior building wall. It does appear that the north and east perimeter yard setbacks are not in compliance with the requirements listed under LUC Sec. 3.2.6.4 perimeter yard indicator "AA". (LUC 3.2.7.2) (LUC Sec. 3.2.6.3)

2. This project contains a total of seven (7) bedrooms as defined by LUC Sec. 6.2.2 (bedroom definition). Seven bedrooms will require five (5) vehicle parking spaces to be provided as described in below comment number four (4). Two (2) vehicle parking spaces are to be provided in the new garage, which results in a deficiency of three (3) on-site vehicle parking spaces. (LUC Sec. 3.5.7.1.G)

3. For all single family dwellings in the R-1 zone with five (or more bedrooms, and for all lots containing two (2) or more single family dwellings, with the second dwelling having more than one bedroom, all parking and maneuvering must be located on-site, either in a side or rear perimeter yard. The vehicular use area must be improved, which includes surfacing, striping, and provisions of barriers in conformance with Development Standard 3-05.0. Parking spaces may not be located in a vehicular use area in any front street perimeter yard. (LUC Sec. 3.5.7.1.H)

4. A variance is required for the approval of alley access. (Zoning Administrator Interpreation)

5. A City prepared covenant, which will run with the land, will be required for this site. The covenant's purpose is to prevent any bedroom from being leased separately. The covenant must be recorded and a copy provided to the Zoning Review Section for DSD records. Please contact me to receive a copy of the covenant.

6. The rear setback listed under the Zoning Information block is labeled as "South" yet the rear property line is located along the north side. Revise as required.

7. If a Board of Adjustment Variance is applied for, provide a copy of the decision letter and list the following information on the site plan: 1) case number 2) date of approval 3) variances granted 4) conditions imposed.


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
09/03/2004 CAGUILA1 BUILDING-RESIDENTIAL REVIEW Needs Review