Review Details: RESIDENTIAL BLDG/ZONING/ENGINE

Permit Number - T04CM03423
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2004 Neil Saunders BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - T04CM03423

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints.
2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure all corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plan

1. Provide window sizes for master bedroom, they may be egress issues due to loss of door.
2. Provide sizes of all new windows sizes including the operable portion of each window.
3. Note that bathtub and shower enclosures shall be finished per P2710 with ceramic tile, or a listed enclosure, to a height of 72" above the drain per R702.4 and R307.2.
4. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per R307.2 (figure).

Foundation Plan

1. Note on the drawings the allowable soil bearing pressure used in the design of the footings, or state that the assumed value of 1500 PSF is being used per table R401.4.1. Footing sizes are based on this assumption.
2. 1/A5, 3/A5 & 4/A5 - minimum 19" footing for 8" CMU wall based on 1500 psf (see comment 1).
3. 4/A5 - Provide bond beam at top of stem wall.

Structural Plan

1. Roof detail on cross section sheet A5 reference sheet A9 - Should reference A8.
2. Special inspection required for epoxy bolts. Submit forms.
3. 2/A8 - Provide blocking between ceiling joists
4. 10/A8 & 3/A8 - Concrete lintel is referenced to 16/A8 - Clarify.
5. Size lintels ML-1 and ML-2.
6. Provide design for concrete lintels.

Mechanical, Plumbing and Electrical Plans

1. Note on plans: Mechanical shall comply with 2000 IRC chapters 18- 24.
2. The City of Tucson has adopted the 1994 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code.
3. Fixture unit calculations - Clotheswasher = 6 units. Add to total. Net change should be -2 (only one shower was deleted).
4. Show locations of smoke detectors per R317. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are removed, existing bedrooms shall be in compliance. When ceiling finish materials are not removed, existing bedrooms shall be equipped with battery operated smoke detectors per R317.1.1.
5. Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used, per E4001.6.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.