Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM03416
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | DENIED 8/9/04 T04CM03416 1. Sheet MP1.0 has been approved by Mechanical/Plumbing Plans Examiner for the installation of Exhaust Fan and Water Heater. These items may not be installed without electrical. Provide electrical design for branch circuits, feeder(s), conduit, conductor, overcurrent protective devices. See the attached. 2. Same as above for lighting fixture on Sheet A-1. May not install the fluorescent fixture without its branch circuit. |
| 08/18/2004 | JIM EGAN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/20/2004 | ANGIE SHOFFSTALL | APPROVAL SHELF | Completed |
| 08/20/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |