Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03411
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 07/23/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/23/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/23/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/23/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 07/23/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 07/23/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | . |
| 07/26/2004 | LLESNY1 | WWM | REVIEW | Passed | |
| 07/26/2004 | JIM EGAN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/26/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |