Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM03393
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2004 | JIM TATE | ENGINEERING | REVIEW | Denied | A copy of the stamped approved site plan must be included in the submittal. |
| 09/20/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the water pipe sizes using the fixture unit values from Table A-2, UPC 1994. |
| 09/20/2004 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/22/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 09/30/2004 | DAN CASTRO | ZONING | REVIEW | Denied | Zoning may not approve the building plans until the site plan has been approved by all sections. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/05/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/05/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |