Permit Number: T04CM03393
Parcel: 113010540

Address:
1301 E ALLEN RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM03393
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2004 JIM EGAN FIRE REVIEW Approved
07/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the plumbing fixture schedule using the fixture unit values from Tables 7-3 and A-2, UPC 1994. Revise the pipe sizes as required.
2. City of Tucson Ordinance 1802 requires a reduced pressure backflow preventer to be located immediately after the water meter. Please show the RPBP on the drawings and include the pressure drop on the water calculations.
3. Revise the size of the water piping to the water heater to reduce the velocity below 8 feet per second. Reference Section A6.1, UPC 1994 and Section 610.0, IAPMO IS 3-93. Note: the specified water heater is incapable of meeting the proposed demand and specified temperature rise.
07/22/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied Provide heat for laundry area. Reference Section 309.1, UPC 2000.
07/22/2004 ROBERT SHERRY WATER REVIEW Approved
07/23/2004 GERRY KOZIOL WWM REVIEW Approved
08/02/2004 JIM TATE ENGINEERING REVIEW Denied A copy of the stamped approved Site Plan must be included in the submittal.
08/02/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
08/24/2004 DAN CASTRO ZONING REVIEW Denied Zoning may not approve the building plans until the site plan has been approved by all sections.
08/25/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS
1) Where is the detail 7/A3.1, shown on sheet A1.1?
2) Some details show laundry roof constructed of wood, and another shows it
constructed of metal. Clarify!
3) Are carports part of this permit? Walls? If so show them on this application.
4) Show the caisson detail as called out on calc`s.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2004 LISA LESNY OUT TO CUSTOMER Approved