Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03354
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/28/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise ventilation calculations to conform to the requirements of Sections 403.3 and 403.3.2, IMC 2000. Show the calculations on a unit by unit basis. |
| 10/20/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM03354 DENIED 10/20/04 1. Provide maintenance receptacles per NEC 210.63. 2. Add 25% for the largest motor on panel load calculations. 3. Sign shall be counted as continuous load on panel load calculations. 4. Provide panel and circuit # of new EFs on electrical plan, and add to panel load calculations. 5. Indicate panel location on plans. |