Permit Number: T04CM03354
Parcel: 117150050

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03354
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
10/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise ventilation calculations to conform to the requirements of Sections 403.3 and 403.3.2, IMC 2000. Show the calculations on a unit by unit basis.
10/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03354 DENIED 10/20/04
1. Provide maintenance receptacles per NEC 210.63.
2. Add 25% for the largest motor on panel load calculations.
3. Sign shall be counted as continuous load on panel load calculations.
4. Provide panel and circuit # of new EFs on electrical plan, and add to panel load calculations.
5. Indicate panel location on plans.