Permit Number: T04CM03343
Parcel: 133263140

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM03343
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2004 Daniel Castro ZONING REVIEW Approved
08/31/2004 Neil Saunders BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T04CM03343

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Site Plan

1. Show sewer, water and gas lines on property. Include location where each enters building.

Foundation Plan

1. Provide landings outside all exterior doors per R312.
2. 2/D-1: Pre-manufactured concrete bell is not an approved method for post foundation. Provide post footing detail (i.e. 16" square footing, 12" into undisturbed soil, 6" min to bottom of post, 2 #4's each way, approved post base, etc)
3. 1/D-1 and #/D-1: show 6" minimum to bottom of sill plate, Callout anchor bolt sizes, spacing and embedment.
4. 4/D-1: Blocking should be at ceiling line. H2.5 should be from ledger to stud. Suggest LUS26 for joist hanger.
5. Callout header size reference for each opening on roof framing plan.
6. 1/A-3 Re-label "Storage".
7. Scales on roof framing plan and Electrical Plan are incorrect.

Electrical and Mechanical Plans

1. Provide receptacle between existing door and window on existing building in new Arizona Room.
2. The dwelling must be provided with heating capable of maintaining a room temperature of 68 degrees at a point 3' above the floor per R303.6. Provide heat source for Arizona Room.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/03/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
09/03/2004 ANGIE SHOFFSTALL REJECT SHELF Completed