Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03304
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2004 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/16/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/16/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/16/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/16/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/16/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM03304 DENIED 7/16/04 1. Provide disconnects for the Insta-Hots per NEC 422 Part III. 2. Update all references to NEC 2002. City started using 2002 beginning 1 July, http://www.ci.tucson.az.us/dsd/Codes___Ordinances/Building_Codes/building_codes.html. 3. Provide circuit for maintenance receptacle for HP-1 per NEC 210.63. |
| 07/16/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/23/2004 | LLESNY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/23/2004 | LLESNY1 | WWM | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/23/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |