Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM03295
Parcel: 141012040

Address:
5343 S CIVANO BL

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM03295
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2005 GERRY KOZIOL WWM REVIEW Approved
06/10/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/13/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show that the specified water closets are capable of operating with a minimum pressure less than 15 PSI. Revise the pipe sizing as required. Reference Section 608.1, UPC 1994.
2. The specified main water supply pipe (1-1/4") is too small to serve the calculated demand with a maximum velocity of 8 FPS. Similarly, 1" PEX can handle a maximum demand of only 14.6 GPM (approximately 21 fixture units) at 8 FPS. Reference Section A 6.1, UPC 1994, Section 610.0, IAPMO IS 3-93, and Section 610.1, IAPMO IS 8-92
3. Revise the drainage of the fixtures located above the rim elevation of the next upstream manhole to not discharge through the backwater valve. Reference Section 710.1, UPC 1994.
4. Comment not addressed. Substitution of alternate piping materials (Plumbing Notes #4) will require the submittal of a revision to the approved plans. Reference Section 301.1.1, UPC 1994.
07/06/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1) Provide notes to framing plan addressing Structural Engineers comments to provide double studs at king studs and between windows per page 11 structural calculations at living room tall wall.
07/07/2005 MICHAEL ST. PAUL ZONING REVIEW Needs Review An approved Development Plan is required.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2005 KMEDINA1 OUT TO CUSTOMER Completed