Permit Number: T04CM03269
Parcel: 13304153A

Review Status: Completed

Review Details: SITE

Permit Number - T04CM03269
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2004 Jim Egan FIRE REVIEW Approved
07/23/2004 JOE LINVILLE NPPO REVIEW Approved
07/23/2004 Joseph Linville LANDSCAPE REVIEW Denied 1) Revise the plans to provide landscape borders and screening per LUC 3.7. and DS 2-06.0.

2) Revise the plans to provide canopy trees in the vehicular use area per LUC 3.7.2.3.A.

3) Revise the plans to demonstrate compliance with the dust control provisions of LUC 3.7.2.7. and LUC 3.7.2.4.A.4.

4) Revise the landscape plan to include the content specified in DS 2-07.0.
08/10/2004 Paul Machado ENGINEERING REVIEW Denied To: Seaver Franks DATE: August 10, 2004
Architects
2552 N. Alvernon Way
Tucson, Arizona 85712

SUBJECT: 9131 E Speedway Blvd, Dental office.
Site plan T04CM03269 (First Review)
T14S, R15E, Section 03

RESUBMITTAL REQUIRED: Site Plan and Drainage Statement.

The Site Plan (SP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
3. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
4. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
5. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
6. Show Activity number (T04CM03269) on all sheets per D.S. 2-02.2.1.29.
7. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
8. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

Drainage Statement:
1. A Drainage Statement is required. A DS is a brief description of drainage conditions applicable for a site which is not affected be 100-year flows of 100 cfs, or more, and is neither subject to detention requirements nor impacted by flows from a significant watercourse per S.M.D.D.F.M., chap. II, 2.1.3.
2. The content and format of the DS should follow S.M.D.D.F.M., chap. II, 2.1.3.
3. Show the project address on the cover of the Drainage Statement.



If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/9131 E Speedway Blvd site
08/17/2004 DAN CASTRO HANDICAP-SITE REVIEW Denied 1. A van accessible parking space is required which conforms to Section 502 of the ICC/ANSI A117.1-1998. In addition, an accessible ramp is required which conforms to Section 405 of the ICC/ANSI A117.1-1998

2. Detail disabled parking space, access aisle, and ramp. Post disabled parking sign. (D.S. 2-02.2.1.A.8)
08/17/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were
addressed. (CODE SECTION/ DEVELOPMENT STANDARD)

1. The following comments are based on a change of use for the existing site resulting in a full code compliance review of the entire site.

2. A total of 23 vehicle parking spaces are required. A total of 22 vehicle parking spaces are provided resulting in a deficiency of one (1) vehicle parking space. (LUC Sec. 3.3.4) (D.S. 2-02.2.1.A.8)

3. A van accessible parking space is required which conforms to Section 502 of the ICC/ANSI A117.1-1998. In addition, an accessible ramp is required which conforms to Section 405 of the ICC/ANSI A117.1-1998

4. Detail disabled parking space, access aisle, and ramp. Post disabled parking sign. (D.S. 2-02.2.1.A.8)

5. Provide wheelstop curbing for parking spaces adjacent to walls and sidewalk areas of less than 6.5 feet wide. Wheelstops shall be located two and one-half (2 ½) feet from the front of the parking space. (D.S. 3-05.2.3.C.2)

6. A five (5) foot wide access aisle measured from the front or rear of the 72 inch long parking space will be provided beside the bicycle parking spaces. (D.S. 2-02.2.1.A.9) (D.S. 2-09.6.2)

7. Label and dimension sight visibility triangles. (D.S. 2-02.2.1.A.10)

8. Dimension the PAAL width. (D.S. 2-02.2.1.A.11)

9. LUC Sec. 3.2.8.4.B requires pedestrian facilities in conformance with D.S. 2-08. A minimum four (4) foot wide accessible sidewalk is required from the right-of-way to the building entrance. (D.S. 2-02.2.1.A.12)

10. Existing sign is located in the existing right-of-way, which will require a Temporary Revocable Easement (TRE) to remain in the right-of-way. If a TRE has been issued, please provide a copy of the document. TRE information may be obtained by contacting the Real Estate Division of the Transportation Department at 791-4181.

11. Indicate by note, whether right-of-way is existing and/or future. (D.S. 2-02.2.1.A.19)

12. Revise the proposed use for dental office as "Medical Service Outpatient subject to Section 3.5.4.8.B." (D.S. 2-02.2.1.A.31)

13. If a Board of Adjustment variance is applied for, please list on the site plan the case number, date of approval, variances granted, and conditions imposed. (D.S. 2-02.2.1.A.38)

14. If applicable, all requested changes must be made to the site and landscape plans. (D.S. 2-07.2.1.A)


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2004 DELMA ROBEY OUT TO CUSTOMER Completed