Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03267
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/16/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 07/16/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 07/22/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/22/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/22/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide listing information for the fire wrap for the grease duct. 2. Provide the installed weight of the hood with support calculations and show how the hood is mounted to the structure. Reference Section 507.6, IMC 2000. 3. Revise the hood exhaust rate to comply with Section 507.13.3, IMC 2000. |
| 07/29/2004 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/29/2004 | EGRANT1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/29/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |