Permit Number: T04CM03263
Parcel: 128010190

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM03263
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please convey to the Owner that no Certificate of Occupancy will be given for the new service until future electrical load(s) is(are) added.
2. It appears that the Main Bonding Jumper for the new electrical service should be 250 MCM, not 4/0. Reference NEC Table 310.16, Table 8, and 250.102 (C).
3. Specify a placard per NEC 230.2 (E), to be installed at the East Elevation Service Section, and the South Elevation Service Section. Provide exact wording for both placards, on the plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2005 KMEDINA1 OUT TO CUSTOMER Completed