Permit Number: T04CM03256
Parcel: 140420760

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03256
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2004 JIM TATE ENGINEERING REVIEW Approved
07/14/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
07/15/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the water piping was sized. Reference Section 610.4, UPC 1994.
2. Include all of the existing fixtures in the fixture unit calculations. Reference Section 610.1, UPC 1994.
3. Show how the new waste lines relate to the existing waste lines on the floor plan. Reference Section 103.2.3, UPC 1994.
07/15/2004 ROBERT SHERRY WATER REVIEW Approved
07/15/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the revised restroom complies with the ventilation requirements of Section 403.3, IMC 2000.
07/29/2004 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
07/29/2004 EGRANT1 WWM REVIEW Needs Review
07/29/2004 EGRANT1 FIRE REVIEW Needs Review
07/29/2004 EGRANT1 ELECTRICAL-COMMERCIAL REVIEW Needs Review