Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03256
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 07/14/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 07/15/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the water piping was sized. Reference Section 610.4, UPC 1994. 2. Include all of the existing fixtures in the fixture unit calculations. Reference Section 610.1, UPC 1994. 3. Show how the new waste lines relate to the existing waste lines on the floor plan. Reference Section 103.2.3, UPC 1994. |
| 07/15/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/15/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the revised restroom complies with the ventilation requirements of Section 403.3, IMC 2000. |
| 07/29/2004 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/29/2004 | EGRANT1 | WWM | REVIEW | Needs Review | |
| 07/29/2004 | EGRANT1 | FIRE | REVIEW | Needs Review | |
| 07/29/2004 | EGRANT1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |